This diagram provides the minimum clearance distances required for installing a Kaden KD24 split system outdoor unit to ensure proper airflow and maintenance access. The unit must be placed at least 30 cm away from the back wall to allow adequate ventilation. A clearance of 60 cm is necessary on the right side for serviceability, while the left side requires 30 cm of space. The front of the unit must have a minimum clearance of 200 cm to ensure unobstructed airflow and efficient heat dissipation. Additionally, a 60 cm gap above the unit prevents heat buildup and allows for proper exhaust. These spacing requirements ensure the unit operates efficiently, preventing overheating and maximizing cooling performance. Proper installation following these guidelines also facilitates maintenance and prolongs the lifespan of the system.