Vaillant ecotec plus 618
This boiler was in a terrible state and considering it had been looked after by a well known company it's a shame to see how much had been missed or just simply ignored.
For starters the turret seal perished and the exhaust was returning back into the boiler giving me an oxygen reading on 19.7 and as the exhaust has been through combustion it's very acidic which has started to rot the boiler from inside out, also as the is not enough oxygen the combustion will be incomplete combustion, which gives you carbon monoxide (the silent killer).
The nut sheared off as I was removing the electrodes, so had to drill out the bolt from the heat exchanger (nightmare) but was successful, I also had to replace the turret, turret seals and flue seals as these had all perished and carried out a full strip down service and finally checked boiler using my flue gas analyser to confirm correct operation.