4hWhat are chiller hookup valves?2 gate valves2 Pressure Gauges2 Thermometer2 AirventsStrainerDrain valve2Flex Connectio...
04/11/2025

4h

What are chiller hookup valves?

2 gate valves

2 Pressure Gauges

2 Thermometer

2 Airvents

Strainer

Drain valve

2Flex Connection

2 dielectric union

Flow switch

A.c / cold room, heat pump, maintenance & service ko lagi call us
30/10/2025

A.c / cold room, heat pump, maintenance & service ko lagi call us

Cause : ❄️ 1. Low Refrigerant Flow / Restriction in the SystemPossible restrictions at the TXV (Thermostatic Expansion V...
05/08/2025

Cause : ❄️ 1. Low Refrigerant Flow / Restriction in the System

Possible restrictions at the TXV (Thermostatic Expansion Valve), filter drier, or capillary tube can reduce refrigerant flow, causing very low pressure on the suction side — which leads to frosting.

Check for blocked or clogged filter drier or strainer inside the TXV.

🔁 2. Evaporator Fan or Airflow Issues

If the evaporator fan is not running or air filters/coils are dirty, it can prevent heat exchange, leading to liquid refrigerant returning to the compressor, causing icing.

Check the indoor blower motor, air filters, and coil cleanliness.

💨 3. Low Refrigerant Charge

Undercharging can cause low suction pressure and improper evaporation, resulting in frosting on the suction line and compressor.

Perform superheat/subcooling tests and pressure readings to confirm.

⚙️ 4. Faulty Thermostat or TXV Malfunction

If the TXV is stuck open or closed, it can cause too much or too little refrigerant to flow into the evaporator.

This again leads to floodback or freezing.

🧊 5. Compressor Floodback

Liquid refrigerant returning to the compressor can cause it to frost over.

This is dangerous and can damage the compressor over time.

🔧 Recommendations:

✅ Check evaporator airflow (blower operation, filters, coils).

✅ Measure suction and discharge pressures.

✅ Check superheat and subcooling.

✅ Inspect TXV/filter drier for blockage or clog.

✅ Ensure correct refrigerant charge using weighing or gauges.

✅ Look for non-condensables or moisture in the system.

30/07/2025
HVAC
02/07/2025

HVAC

Notes,,,,
02/07/2025

Notes,,,,

Address

Gandaki
Pokhara
33800

Opening Hours

Monday 08:00 - 18:00
Tuesday 08:00 - 18:00
Wednesday 08:00 - 18:00
Thursday 08:00 - 18:00
Friday 08:00 - 18:00
Sunday 08:00 - 18:00

Telephone

+9779845785787

Alerts

Be the first to know and let us send you an email when Sanrit&Senisa Air Care Mantennce Service Center Pvt.ltd posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to Sanrit&Senisa Air Care Mantennce Service Center Pvt.ltd:

Share