05/19/2026
Had a service call with the complaint that the compressor wasn't coming on. Upon inspection we found it had shorted out and blew off one of the harness pins and leaked all the refrigerant out, the only option was to replace the unit. We replaced it with an Amana 80% furnace and 15 Seer AC with a lifetime warranty, we also replaced the copper lineset because the previous installers left a 50 foot line set and had it just laying on the ground when the space only needed 18 feet, we also replaced the drain line because it ran up hill then downhill then up again, we replaced the whip to the disconnect and the communication wire out to the condenser, along with the return air plenum, and the ¾ plywood underneath the unit and added a 4 inch insulated sheet metal riser in place of the 2x4's that the unit was sitting on. Overall the customer is ecstatic with the new system. Call us for any of your heat and air needs