REQUIRED EXIT WIDTH vs UNIT OF EXIT WIDTH
Ulang siaran ni dan harapnya ada penjelasan lanjut dari posting saya SELECTING AND CALCULATING EXIT WIDTHS pada 08 January 2024.
UBBL 1984 under By-Law 181 Width of Means of Egress states that
egress to be measured in units of exits width of 550 millimetres.
* It means 1 unit width = 550mm
+ Fractions of a unit is counted as half of a unit exit width = 300mm,
* BUT no individual access to exit, i.e., corridors, doors and staircases width, to be less than 700mm.
* Maksudnya, syarat wajib bukaan laluan keluar tidak boleh kurang dari 700mm lebar.
* Jangan abaikan nota di bawah 7th Schedule CALCULATION OF AN OCCUPANT LOAD AND CAPACITY OF AN EXIT di bawah Nota (3).
Lebar bukaan laluan keluar bukan bukaan bingkai pintu semata-mata tetapi baca
Nota (3) Dalam menentukan unit lebar tempat keluar bagi suatu muka pintu tempat keluar, hanya jumlah lebar bersih muka pintu itu hendaklah diambil apabila pintu itu dalam keadaan terbuka.
* Sila ambil maklum lebar bingkai pintu rintangan api yang digunakan. Biasanya lebih kurang 65mm ketebalan bingkai pintu rintangan api dan daun pintu rintangan api yang biasanya berketebalan 45-48mm.
* Nota: Untuk reka bentuk pembinaan, ofis kami andaikan tebal pintu 50mm untuk pastikan pematuhan pintu rintangan api. Jadi kami tambah 180mm lagi [65mm bingkai kiri + 65mm bingkai kanan + 50mm tebal pintu kepada bukaan diperlukan untuk pintu rintangan api untuk 1 daun pintu]. Untuk pintu 2 daun kena tambah ketebalan pintu satu lagi menjadikan 230mm tebal bingkai² dan pintu² sebelum ukuran unit lebar bersih laluan tempat keluar.
Sebagai contoh, jika untuk kiraan keperluan minimum bukaan laluan melalui pintu 1 daun ialah 700mm, kami tambah 180mm untuk bingkai dan daun pintu menjadikan bukaan untuk bingkai pintu menjadi 880mm agar bukaan bersih patuh UKBS mendapat kelebaran bersih minimum 700mm yang diperlukan untuk pintu dalam keadaan terbuka.
NOTE:
(1) An exit is measured in units of 550 milimetres width and the width of the access to the exit shall be at least 700 milimetres.
(1A) For a hospital or nursing home, the minimum clear width of an exit door opening ... to refer to By-Law 224A Hospital.
(2) For a place of assembly, the main exit shall be 50 percent of the total required exit width.
(3) In determining the unit of exit width for an exit doorway, only the total clear width of the
doorway shall be taken when the door is in the open position is to be measured.
We derive the unit width by taking the Occupant Load and DIVIDE by the capacity of exit whether it is an opening or a DOOR [HORIZONTAL] or RAMP or STAIRCASE [VERTICAL] exits.
I noticed that many architects wrongly calculate Occupant Load by jumbling the formula.
Ada ajaran sesat oleh sesiapa ke ni?
Read my notes under By-Law 176 (a) and (b) below.
UBBL By-Law 176 Computing Storey Exit Width states HOW to compute the required exit width from individual floors of a building clearly,
(a) calculate the floor area net or gross whichever is applicable - Refer 7th Schedule, if the table in 7th Schedule state net, calculate only
EITHER
* the Net Floor Area [NFA], which can be any % of floor efficiency between 50% and 90%, depending on building types and design.
OR
* If the table state as Gross then calculate the overall or Gross Floor Area [GFA].
OR
* Only that there is a Gross (4) in the table which denotes that it is actually a modified NFA which EXCLUDE areas occupied by a staircase, lift, sanitary accommodation or any other space occupied by machinery for any lift, air conditioning system but INCLUDE lobbies and corridors and other common areas which may be turned into habitable spaces.
Note:
Use the required area calculations. Clients may not appreciate it if we use GFA for calculations for exit width when the By-Laws only require NFA. The difference in the sizes of exits may be between 10% and 50%. They may lose usable areas unnecessarily due to too wide corridors, doors and staircases.
(b) determine the allowable occupancy load factor from Table;
7th Schedule CALCULATION OF AN OCCUPANT LOAD AND CAPACITY OF AN EXIT has a confusing title for the 2nd column after 1st column 'Purpose group' which is TITLED,
'Occupant load square metre per'
The title just mean the numbers under the column represent the area occupied by a person.
e.g.,
* 1.5 net, under the column, means allow 1.5sqm NFA for a person,
* 20 gross, under the column, means allow 20sqm GFA for a person, and
* 6 gross (4), under the column, means allow 6sqm GFA for a person, but EXCLUDE areas for staircases, lifts, toilets, spaces for machinery such as lifts and air conditioning system but INCLUDE lobbies and corridors and other common areas which may be turned into habitable spaces. The Note 'gross (4)' if you notice is actually a modified NFA.
You can read my earlier posts on this GFA vs NFA etc.
SELECTING AND CALCULATING EXIT WIDTHS posted in 08 January 2024.
(c) divide the floor area by the number of square metre per person to determine the number of persons for which exits must be provided for that floor;
* Eventhough it is straight forward, this statement has resulted in many architects calculate the requirements wrongly.
* It just means, the FLOOR AREA, calculated as GFA or NFA or Modified NFA, is to be DIVIDED with the occupancy load factor under (b).
e.g.,
GROSS FLOOR AREA = 1000sqm
Occupancy Load Factor from 7th Schedule = 20sqm gross / person
Occupany Load = 1000sqm / 20sqm gross / person = allow 50 persons for the floor.
(d) determine from the table the capacity of the type of exit to be used for the purpose group being designed;
* Once we calculated the number of persons for the floor, we take a look the last column in the 7th Schedule, which are titled as CAPACITY EXIT with 5 sub-columns titled as follows:
Door outside | Horizontal exit | Ramp main exit | Ramp second exit \ Stairs
* Choose the relevant CAPACITY EXIT for the corresponding PURPOSE GROUP.
e.g.,
if the exit is a staircase, and say, the number is 60 for the Purpose Group
and
(e) calculate the number of units of exit width for each type of exit used based upon the capacity.
e.g.,
* say, the number is 60 persons per unit width for the Purpose Group,
then taking the Occupancy Load from above example under (c), which is 50 persons for the floor, then we calculate as below
* Occupancy Load of 50 persons DIVIDED WITH the capacity exit of
60 persons per unit width = unit width required.
* 50 persons / 60 persons per unit width = 0.83 unit width
* A fraction number is taken as half a unit width = 300mm
* BUT no individual access width to exit to be less than 700mm hence instead of 300mm as calculated, the minimum width of the exit = 700mm.
EXCEPT there is a requirement under UBBL By-Law 177 Computing number of staircases and staircase width which states,
(e) at least one of the staircases should be a minimum of two units width [i.e., 550mm per unit x 2 units = 1100mm] except that 900 millimetres may be allowed where total occupancy of all floors served by staircases is less than 50;
By-Law 174 Arrangement of storey exits states, and By-Law 168. Staircases state
(1) Except as provided for in by-law 194, every compartment shall be provided with at least two storey exits located as far as practical from each other and shall not be less than 5 metres apart ...
* Reading By-Laws 174, 176 and 177 together, from the above calculations, it means that even though we calculated and may design a staircase with the minimum width of 700mm, there should be another staircase with a minimum width of 1100mm, WITH THE EXCEPTIONS if the total occupancy of all floors for the building is COMBINED and the number of persons is LESS THAN 50 persons, then we have the option to design for a 900mm wide staircase with a 700mm wide staircase.
DON'T FORGET
By-Law 168 Staircases
(2) Staircases to be of a width that in the event of any one staircase is not availabe for escape purposes, the remaining staircases to accommodate the highest occupancy load of any one floor discharging into it ...
* AT ALL TIMES if any one staircase cannot be used, the balance number of staircases MUST BE ABLE to accommodate the Occupancy Load of the floor.
* It means that if there are only 2 staircases, BOTH staircases MUST BE SIZED to the required FULL capacity and exit width. If there are 3 staircases, then the total width of 2 out of 3 staircases MUST BE SIZED to the required FULL capacity and exit width.
Hopefully, our architects calculating staircase width take note of these and other requirements when designing staircases.
Oh ya .. kalau untuk GROUND FLOOR at STREET LEVEL, kita terus tengok dan kirakan keperluan lebar DOOR OUTSIDE. Tak perlu la kira pulak exit width untuk tangga .. tangga nak ke mana pulak kan ..
Dan jangan lupa lantai berkenaan masih perlu 2 jalan keluar walapun bangunan SINGLE STOREY atau lokasi berada di GROUND FLOOR .
By-Law 166 Exits to be accessible at all times
(1) .. not less than two separate exits shall be provided from each storey together with such additional exits as may be necessary.
Dalam masa yang sama, bila kita reka bentuk satu lantai untuk keluar melalui tangga, jangan lupa kirakan juga kelebaran pintu rintangan api ke tangga menggunakan kiraan HORIZONTAL EXIT sebelum kira kelebaran tangga.
LEBAR PINTU juga mesti patuh kehendak UKBS/UBBL untuk kelebaran laluan keluar selain kita patuhi kehendak LEBAR TANGGA.

Boleh rujuk juga postings saya ini
1. https://www.facebook.com/share/p/1GiqeuTKjp/
2. https://www.facebook.com/share/p/1DwZMgLuQH/
3. https://www.facebook.com/share/p/1UuqL465nB/

28/10/2026
2027
28/10/2026

2027

Borang Renew Permit Pembinaan
20/10/2026

Borang Renew Permit Pembinaan

18/10/2026

Kuala Lumpur City Hall (DBKL) failed to obtain a stay on the High Court’s April decision ordering it and the wound-up developer, Fame Modulation Sdn Bhd, to pay RM1.3 million in damages to two former civil servants.

Address

Lot 298, Lorong 49C, Bukit E, Kg Cheras Baru
Kuala Lumpur
56100

Opening Hours

Monday 09:00 - 17:00
Tuesday 09:00 - 17:00
Wednesday 09:00 - 17:00
Thursday 09:00 - 17:00
Friday 09:00 - 17:00
Saturday 09:00 - 01:00

Telephone

+60129077320

Alerts

Be the first to know and let us send you an email when Yasir Design Works posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to Yasir Design Works:

Shortcuts

Share